Build your professional network on facebook via our app Go to app
 
 
 
Industry : Oil & Gas
Keywords :

control valve

Activity:  0 comments  2838 views  last activity : 07 06 2010 20:18:04 +0000
Share
 
 
 

ACCESSORIES

9.1 GENERAL

The accessories discussed in this section should be supplied with the valve. This “total

supply” will allow functional testing at the factory, particularly of stroking times.

The accessories may be installed on a separate mounting plate to allow removal of just the

valve and actuator, thus reducing risk of damage to the accessories.

The requisition shall indicate from which side(s) the valve and its accessories will be

accessible after installation.

Control valve accessories are considered to be instruments and shall therefore comply with

the applicable requirements of DEP 32.31.00.32-Gen.

9.2 VALVE POSITIONERS

Intelligent electro-pneumatic valve positioners (input signal 4 mA to 20 mA) should be used.

If the use of a control valve performance management system is considered, or such a

system is already in use, standardisation on one make of intelligent valve positioner is often

required. In these instances, the control valve specification shall specify details (i.e., make,

model, level of intelligence) of the required intelligent positioner.

If the positioner is not of the same make as the control valve, the control valve

Manufacturer shall be responsible for the correct software settings in the configuration (i.e.

characteristic, stroke etc.) of the positioner.

For split range applications, the range “split” should reside in the DCS and each of the

valves should receive a 4 mA to 20 mA input signal.

The positioner output shall be direct-acting unless otherwise specified.

The positioner shall not be provided with a bypass valve. The positioner shall have a

weatherproof enclosure with a degree of protection of at least IP 55 in accordance with

IEC 60529.

The valve positioner shall have sufficient capacity in both directions for pressuring and

venting the actuator to maintain the specified response times.

The Manufacturer shall, upon request, specify the air quality, consumption and filter

requirements for the elements supplied with the valve.

Tubing between the positioner output and the actuator, or between accessories and the

actuator, shall be as follows:

- the control valve Manufacturer shall determine the tubing diameter so as to achieve the

required stroking times. The minimum tubing diameter shall be 6 mm (1/4 in.). The

tubing shall comply with the specification given in the requisition. Bare copper tubing

shall not be used. For areas with a potential H

offshore application, or other corrosive atmosphere locations, tubing and fittings shall be

of stainless steel or other materials suitable for the stated atmospheric conditions and

shall be subject to the Principal's approval.

- all compression fittings in a plant shall be of the same size, make and type. Mixing of

fittings of different size (e.g. metric with imperial) or make/type will result in unreliable

joints; the make/type is subject to the Principal's approval.

The valve positioner shall be provided with an identification plate, marked with the air

supply pressure and input signal.

The combination of a separate electro-pneumatic convertor and a pneumatic valve

positioner should be avoided. If this is unavoidable, the output range of the converter and

the input required on the pneumatic valve positioner shall be checked in order to prevent

possible instability.

DEP 32.36.01.17-Gen.

April 2003

Page 27

9.3 HAND WHEELS

Control valves shall only be provided with a hand wheel if required for operational reasons.

If a hand wheel is required, it shall comply with the requirements specified in the MESC

additional requirements (SPEs).

The hand wheel of a control valve with de-clutch facilities shall be provided with an

instruction plate explaining how it is to be used. When de-clutched, the hand wheel shall

not interfere with the full stroking action of the control valve.

9.4 LIMIT STOPS

Limit stops shall be mechanical devices, mounted on the valve or actuator. They shall be

constructed so that hand wheel operation does not allow travel/rotation beyond the limit

stop setting. Bolts screwed in the body shall not be used as a limit stop.

Limit stops shall be adjustable from outside and fitted with a locking facility, e.g. a locking

nut, to prevent tampering or loosening. The limit stops shall be adequately protected

against unintentional adjustments.

The Manufacturer shall set the limit/travel stops at the required minimum or maximum valve

opening.

9.5 LOCK-UP VALVES

Air lock-up valves shall be specified for all services requiring the control valve to remain in

position in case of instrument air supply failure.

To prevent unintentional adjustments, the lock-up valves shall have a bolt adjustment

provided with a locking facility, e.g. a locking nut.

The lock-up valves shall be set 0.5 bar above the minimum instrument air supply pressure

required by the actuator.

For control valves with a valve positioner, the lock-up valve shall be installed between the

positioner output and the actuator. If lock-up valves are fitted on valves operated by a

solenoid valve, the solenoid valve shall be installed between the lock-up valve and the

actuator.

9.6 LIMIT SWITCHES

If limit switches are required, they shall be of the proximity type. The proximitor(s) and

initiator should be mounted inside a box for mechanical protection. The flying leads of the

proximitor(s) shall terminate in an attached terminal box; alternatively, the protection box

and the terminal box may be combined into one box. These boxes shall be suitable for the

electrical hazardous area classification in which they are located.

If not armoured, the flying leads shall be protected against mechanical damage.

If fitted, the external linkage between the actuator stem or rotary spindle and the initiator

shall be protected against unintentional damage.

Proximity switches shall be in accordance with DIN 19234.

The valve Manufacturer shall follow the mounting instructions supplied by the limit switch

Manufacturer. The valve Manufacturer shall properly adjust the limit switches. The vanes

should approach the proximity switch perpendicular on its axis.

Due consideration shall be given to the discrimination between the “closed” and “not

closed” status of valves, especially for rotary valves without a dead angle, linear motion

valves and valves with quick opening characteristics, with respect to the process

requirements of the flow to be detected.

Proximity switches shall be adjustable and shall function autonomously, e.g., one switch for

the "fully open" position and a separate switch for the "fully closed" position.

DEP 32.36.01.17-Gen.

April 2003

Page 28

2S or acetylene atmosphere, or for

NOTE: If proximity switches are installed to detect a partially-open valve position, the vane shall be shaped so

that a distinction can be made whether or not the partial open position has been reached/passed.

Example: If an 80 % open position is to be detected, a logic ‘0’ might represent a valve opening

between 0 % and 80 % and a logic ‘1’ not just a valve opening at 80 %, but any valve position of 80 %

and above.

The combination of proximitor and proximitor circuit shall be of fail-safe design for

applications with a Safety Integrity Level 1 and above (see DEP 32.80.10.10-Gen.). For all

other applications, fail-safe design is preferred, but cost aspects may justify the use of

non-fail-safe limit switches.

NOTE: If fail safe and non-fail safe limit switches are applied in a project, the fail-safe design should be used

for all switches connected to the IPS and the non-fail-safe design for all other switches. This practical

approach will provide flexibility during the engineering phase and limits the variety of input cards for

IPS and DCS.

9.7 INSTRUMENT AIR BUFFER VESSELS

9.7.1 General

Dedicated local instrument air buffer vessels are required for springless actuators of control

valves, variable-pitch fans and dampers, if they must be driven to or held in a predefined

position in the event of instrument air failure.

Such air buffer vessels may also be required for actuators with springs to make them

instrument air failure robust.

Two types of design can be distinguished: Secured Instrument Air (SIA) design and the

Manufacturer’s standard air buffer design. Plant safety reviews (e.g. a HAZOP or HSE desk

review) should identify the applications for which a secured air supply is needed.

NOTE: An air buffer vessel may require a safety relief device.

9.7.2 Secured Instrument Air design

The secured instrument air supply shall maintain sufficient instrument air pressure in the

buffer vessel to allow for at least three valve strokes within 30 min. Unless otherwise

specified, the capacity of the secured instrument air buffer vessel shall be sized for a

minimum pressure of 4.2 bar (ga) in the instrument air header.

NOTE: One valve stroke is a movement from the fully open position to the fully closed position or vice versa.

The specific design requirements for secured instrument air buffer vessels and associated

instruments for depressuring systems, as discussed in DEP 32.45.10.10-Gen, apply to all

applications requiring secured instrument air. The Principal shall approve air buffer vessel

capacity calculations.

9.7.2 Manufacturer’s standard air buffer design

For applications where the Manufacturer’s standard air buffer vessel designs are

acceptable, the air buffer vessel capacity shall be sized for a minimum pressure of

4.2 bar (ga) in the instrument air header. The Principal shall approve air buffer vessel

capacity calculations.

9.8 AIR LUBRICATORS

Air lubricators shall be considered for pneumatic long-stroke cylinder actuators.

Air lubricators shall be of the oil-mist type and the oil flow shall be externally adjustable.

The oil buffer capacity shall be sufficient for continuous operation for one month.

In addition, the lubricator shall have facilities for oil refilling under pressure, shall have oil

level indication and shall be suitable for installing on a mounting plate.

If air lubricators are used for valves operated by a solenoid valve, the lubricator shall be

installed upstream of the solenoid valve.

DEP 32.36.01.17-Gen.

April 2003

Page 29

Spherical glass (bowl type) air lubricators shall not be used.

9.9 SOLENOID VALVES

If solenoid valves are required, they shall be provided with a disc and/or seat of resilient

material to achieve TSO. The air passages in the solenoid valves and the air tubing shall be

large enough to achieve the opening or closing time of the valve as specified. If this would

lead to unrealistically large passages and consequently high power consumption of the

solenoid valve, consideration should be given to the use of quick-exhaust valves.

To prevent plugging (e.g. during freezing periods), solenoid valves shall not be supplied

with exhaust port protectors. Instead, they shall be provided with a piece of tubing bent

downwards with the end cut off at an angle of 45°.

Solenoid valves with flying leads shall be provided with a terminal box. If not armoured, the

flying leads shall be protected against mechanical damage.

To limit induction, DC solenoids shall be de-coupled with shunt diodes, connected directly

across the solenoid terminals.

For control valves with a valve positioner, the solenoid valve shall be installed between the

positioner output and the actuator.

Solenoid valves should be direct-operated. For large-volume actuators, a combination of a

standard solenoid valve and separately mounted, pneumatically operated switching valve is

preferred for its robustness to the use of a pilot-operated solenoid valve.

If a pilot-operated valve is used, the air supply to operate the pneumatic valve should not

be derived internally from the solenoid operated pilot valve, but from an external air supply

connection. The use of pilot-operated solenoid valves requires the approval of the Principal.

9.10 FILTER REGULATORS

An air filter regulator shall be installed in the instrument air supply line to the valve if the

valve, actuator and/or accessories cannot operate safely at the upper design pressure of

the instrument air header, see (8.1).

NOTE: If the instrument air system is provided with relief valve(s), the upper design pressure of the

instrument air header is the set pressure of such relief valve(s).

The air filter regulators shall be of the reducing-relief valve type, with drainage facility and

bolt adjustment provided with a locking facility, e.g. a locking nut, to prevent tampering.

The air filter cartridges shall be of the rigid structure type to resist channelling, rupturing,

shrinkage or distortion and shall have a maximum mesh size of 40

The capability, e.g. output capacity and required spring range, of the filter-regulator shall be

checked against the instrument air requirement of the particular positioner and/or actuator

or pneumatic instrument.

Glass (bowl-type) filter regulators shall not be used.

Filter regulators shall be mounted in the vertical position so that they are self-draining.

Air filter regulators shall be fitted with small pressure gauges indicating the incoming

instrument air supply pressure and delivery pressure to the actuator and/or its components.

9.11 FILTERS

An air filter (i.e. without regulator) should be installed in the instrument air supply line to the

valve if the valve, actuator and accessories can operate safely at the upper design pressure

of the instrument air header.

The air filter shall be provided with a manual drainage facility and a filter cartridge of the

rigid structure type, to resist channelling, rupturing, shrinkage or distortion, and having a

maximum mesh size of 40

DEP 32.36.01.17-Gen.

April 2003

Page 30

Glass (bowl type) filters shall not be used.

Filters shall be mounted in the vertical position so that they are self-draining.

Air filters shall be fitted with small pressure gauges indicating the incoming instrument air

supply pressure and delivery pressure to the actuator and/or its components.

9.12 QUICK-EXHAUST VALVES

Quick-exhaust valves may be provided for on-off services that require the control valve to

open or close faster than is possible with a standard actuator configuration. Fitting quick

exhaust valves to throttling services may result in unstable operation and is therefore not

recommended.

Pilot-operated quick-exhaust valves shall not be used.

To prevent plugging (e.g. during freezing periods), quick-exhaust valves shall not be

supplied with exhaust port protectors. Instead, they shall be provided with a piece of tubing

bent downwards with the end cut off at an angle of 45°.

Quick-exhaust valves shall be fitted directly to the port of the actuator.

9.13 VOLUME BOOSTERS

High capacity volume boosters shall only be provided if needed to achieve the specified

stroking times.

9.14 RESTRICTORS

If a throttling valve is required to be opened or closed slowly, this functionality should be

implemented in the DCS or other remote electronic system. Mechanical instrument air

restrictors should not be used for throttling valves.

If used, a mechanical flow restrictor shall be provided with a lockable, variable restriction.

For uni-directional restrictors, the direction(s) of restricted flow shall be indicated by a

permanent mark on the body.

If an air flow restrictor is fitted on a control valve equipped with a solenoid valve, care shall

be taken in locating the restrictor relative to the solenoid valve. The restrictor shall only

affect the required slow-opening or slow-closing of the control valve and shall not influence

the other (unrestricted) valve movement.

DEP 32.36.01.17-Gen.

April 2003

Page 31

μm.μm.

10. VALVE MARKING

The control valve shall be provided with a standard stainless steel identification plate,

showing the mandatory and supplementary marks as defined in IEC 60534-5.

In addition, the TSO direction(s) shall be clearly marked where applicable by a permanent

mark cast in or stamped on the valve body. Painted marks are not acceptable.

Three-way valves shall clearly indicate the common inlet or common outlet port by a

permanent mark "COMMON" stamped on the flange.

Control valves affecting operational safety shall have warning plates, with text in white

letters on a red background and stating, as appropriate, either:

WARNING

TRIM SIZE AFFECTS RELIEF VALVE CAPACITY

or

WARNING

TRIM SIZE AFFECTS FIRING OF FURNACE

Warning plates shall be attached by screws or rivets.

DEP 32.36.01.17-Gen.

April 2003

Page 32

11. INSPECTION AND TESTING

11.1 EXTENT

The Manufacturer shall perform the following inspections and production tests (see Notes 1

through 4):

Inspection/test Extent

Method and

acceptance criteria

Examination and

certification

Valves in general service

(as defined in MESC SPE 77/302)

MESC SPE 77/302

Valves in special services

(as defined in MESC SPE 77/303)

MESC SPE 77/303

Dimensional inspection All valves (11.2)

Hydrostatic test All valves (11.3)

Functional test All valves (11.4)

Hysteresis and dead

band test for throttling

valves

Random sample (Note 4) (11.5)

Seat leakage test

Valves with Class V or Class VI tight

shut-off requirement

All valves

(11.6)

Other valves Random sample (Note 4)

Capacity test Random sample (Note 4) (11.7)

Low temperature test Valves with a lower design

temperature ranging from

minus 30 °C to minus 196 °C

Type approval testing in

accordance with

specification T-2.253.730

Production testing:

Sample in accordance

with MESC SPE 77/306

(11.8)

Vacuum test Valves in vacuum service Sample in accordance

with MESC SPE 77/307

MESC SPE 77/307

Fugitive emission test Valves used in services requiring a

fugitive emission limitation

Sample in accordance

with MESC SPE 77/312

MESC SPE 77/312

NOTES: 1. The selected valves for each test shall be listed by the Contractor and approved by the Principal.

2. Inspection and testing shall include accessories if part of the supply.

3. The test results shall be made available as part of the package of final certified documents.

4. The Principal shall approve the number of valves sampled.

11.2 DIMENSIONAL AND FLANGE FACE FINISH CHECK

The face-to-face dimensions shall be as given in the relevant standard (4.4). All dimensions

(including overall height) shall be as shown on the Manufacturer's drawings.

The flange face finish shall be checked (4.3).

11.3 HYDROSTATIC TEST

Hydrostatic testing shall be in accordance with IEC 60534-4, with the test duration as

follows:

Valve size Test duration

DN 80 to DN 200 2 min

DN 50 1 min

DEP 32.36.01.17-Gen.

April 2003

Page 33

For carbon steel valves and low alloy steel valves, the hydrostatic test fluid shall be potable

water with a chloride content of maximum 200 mg/kg. Austenitic and duplex stainless steel

valves and valves made of 9 % nickel alloy shall be hydrostatically tested with potable

water with a chloride content of 50 mg/kg or less. These valves shall be flushed with

condensate or demineralised water (chloride content of 2 mg/kg maximum) immediately

after the hydro test. All valves shall be drained immediately after the test and shall be

thoroughly dried immediately after draining.

11.4 FUNCTIONAL TEST

The control valve shall be completely assembled and fitted with all accessories such as

positioner, solenoid valve(s), etc.

The valve positioner shall be checked for correct calibration.

The stroking time at the specified air pressures shall comply with the requirements given in

this document (see 8.3). All required stroking times shall be checked during the fuctional

testing.

If the control valve is equipped with a hand wheel, it must be possible to fully open and

close the valve using the hand wheel; see (9.3).

If the control valve is equipped with limit switches, they shall be checked for functional

operation with a proximity tester.

11.5 HYSTERESIS AND DEAD BAND TEST

For definitions and test procedures, refer to IEC 60534-1 and IEC 60534-4.

The actuating medium for the tests shall be clean, dry air or nitrogen. Testing shall be

performed under atmospheric conditions (at zero differential pressure and ambient

temperature) and with the minimum specified air supply pressure.

The

following sequence of input signals: 50 %, 75 %, 100 %, 75 %, 50 %, 25 %, 0 %, 25 % and

50 %. For PTFE-based packing, the hysteresis shall not exceed 1.0 % of maximum valve

stroke.

The

5 %, 50 % and 95 % of the input span. For PTFE-based packing, the maximum dead band

found shall not exceed 2 % of rated input signal.

For packing other than PTFE, the maximum hysteresis and dead band shall be quoted by

the Manufacturer for approval by the Principal.

All test results shall be documented.

11.6 SEAT LEAKAGE TEST

The seat leakage test shall be in accordance with IEC 60534-4, with the acceptance criteria

for the specified shut-off class; see (3.1) for TSO class V or VI. If the shut-off class is not

specified, the following acceptance criteria shall apply:

DN 250 3 minhysteresis test shall consist of measuring the valve stem position in response to thedead band is expressed as a percentage of the input span and shall be measured at

Acceptance criteria

Single-seated valves Class III

Double-seated valves Class II

For each valve tested, the Manufacturer shall state the following data:

- flow direction;

- test medium;

- test differential pressure;

DEP 32.36.01.17-Gen.

April 2003

Page 34

- seat leakage flow rate measured;

- allowable seat leakage flow rate;

- seat leakage class (if applicable).

11.7 CAPACITY TEST

The actual C

11.8 LOW TEMPERATURE PRODUCTION TEST

Low temperature production testing shall be in accordance with MESC SPE 77/306.

In addition, a hysteresis and dead band test (11.5) shall be performed at the temperature of

the low temperature test.

11.9 WITNESSING BY PRINCIPAL

The extent of the Principal's involvement in witnessing inspections and tests at the

Manufacturer's works shall be stated in the requisition.

DEP 32.36.01.17-Gen.

April 2003

Page 35

v value shall be demonstrated by a test in accordance with IEC 60534-2-3.

12. DOCUMENTATION

The document requirements to record the valve selection process (2.2) shall be as

specified in the requisition. It should include at least:

- calculations of control valve capacity (C

where applicable, details of the secured instrument air vessel;

- details of the selected actuator and torque or thrust figures;

For spare part requirements, see DEP 70.10.90.11-Gen

v), calculations of the predicted noise level, and,

 
0 comments on "CONTROL VALVE - SELECTION-SIZING AND SPECIFICATION PART IV"
Add your comment on "CONTROL VALVE - SELECTION-SIZING AND SPECIFICATION PART IV"

Rate:
Submit
Leading Recruitment Firm
Leading Recruitment Firm
Viewers also viewed
Air pollution in Indian cities is growing by leaps and bounds. Shillong is the lest polluted...
 
0 referals 73 arguments, 3226 views
Mind vs Brain
 
192 referals 5 arguments, 100 views
Indians shell out the most in the world for petrol! Already there are a lot of difficulties,...
 
2848 referals 27 votes, 791 views
more...  
Recent Knowledge (69)
5 NICE LITTLE STORIES.....                                                                      ...
0 referals 12 comments, 467 views
Look At Yourself After Watching this Video Every Child is Special ....Just Open UR EyeZ :)  
 
844 referals 16 comments, 250 views
In today's news, I came across this article that scientists at Sandia National Labs who were...
0 referals 5 comments, 163 views
more...  
More From Author
The difference between whole current meter and CT meter is whole current meter is without current transformer and the CT meter is with current transformer (CT).
Whole current meter will measure the actual current directly without using the transformer. CT meter will have current transformer to reduce the high current to low current and the meter connected to CT will give the reduce current reading equivalent...
A poor man had no land and prayed to God for some land. God appeared to him and told him that all that he could cover from dawn to dusk would be his land. The man set off the next morning without sleeping a wink. Though he had covered enough land...
more...