Energy Professionals |
International Oil & Gas Professionals Hub |
POWER PROFESSIONALS |
7 more ...|
|
||
|
Activity:
0 comments
2838 views
last activity : 07 06 2010 20:18:04 +0000
|
||
|
|
ACCESSORIES 9.1 GENERAL The accessories discussed in this section should be supplied with the valve. This “total supply” will allow functional testing at the factory, particularly of stroking times. The accessories may be installed on a separate mounting plate to allow removal of just the valve and actuator, thus reducing risk of damage to the accessories. The requisition shall indicate from which side(s) the valve and its accessories will be accessible after installation. Control valve accessories are considered to be instruments and shall therefore comply with the applicable requirements of DEP 32.31.00.32-Gen. 9.2 VALVE POSITIONERS Intelligent electro-pneumatic valve positioners (input signal 4 mA to 20 mA) should be used. If the use of a control valve performance management system is considered, or such a system is already in use, standardisation on one make of intelligent valve positioner is often required. In these instances, the control valve specification shall specify details (i.e., make, model, level of intelligence) of the required intelligent positioner. If the positioner is not of the same make as the control valve, the control valve Manufacturer shall be responsible for the correct software settings in the configuration (i.e. characteristic, stroke etc.) of the positioner. For split range applications, the range “split” should reside in the DCS and each of the valves should receive a 4 mA to 20 mA input signal. The positioner output shall be direct-acting unless otherwise specified. The positioner shall not be provided with a bypass valve. The positioner shall have a weatherproof enclosure with a degree of protection of at least IP 55 in accordance with IEC 60529. The valve positioner shall have sufficient capacity in both directions for pressuring and venting the actuator to maintain the specified response times. The Manufacturer shall, upon request, specify the air quality, consumption and filter requirements for the elements supplied with the valve. Tubing between the positioner output and the actuator, or between accessories and the actuator, shall be as follows: - the control valve Manufacturer shall determine the tubing diameter so as to achieve the required stroking times. The minimum tubing diameter shall be 6 mm (1/4 in.). The tubing shall comply with the specification given in the requisition. Bare copper tubing shall not be used. For areas with a potential H offshore application, or other corrosive atmosphere locations, tubing and fittings shall be of stainless steel or other materials suitable for the stated atmospheric conditions and shall be subject to the Principal's approval. - all compression fittings in a plant shall be of the same size, make and type. Mixing of fittings of different size (e.g. metric with imperial) or make/type will result in unreliable joints; the make/type is subject to the Principal's approval. The valve positioner shall be provided with an identification plate, marked with the air supply pressure and input signal. The combination of a separate electro-pneumatic convertor and a pneumatic valve positioner should be avoided. If this is unavoidable, the output range of the converter and the input required on the pneumatic valve positioner shall be checked in order to prevent possible instability. DEP 32.36.01.17-Gen. April 2003 Page 27 9.3 HAND WHEELS Control valves shall only be provided with a hand wheel if required for operational reasons. If a hand wheel is required, it shall comply with the requirements specified in the MESC additional requirements (SPEs). The hand wheel of a control valve with de-clutch facilities shall be provided with an instruction plate explaining how it is to be used. When de-clutched, the hand wheel shall not interfere with the full stroking action of the control valve. 9.4 LIMIT STOPS Limit stops shall be mechanical devices, mounted on the valve or actuator. They shall be constructed so that hand wheel operation does not allow travel/rotation beyond the limit stop setting. Bolts screwed in the body shall not be used as a limit stop. Limit stops shall be adjustable from outside and fitted with a locking facility, e.g. a locking nut, to prevent tampering or loosening. The limit stops shall be adequately protected against unintentional adjustments. The Manufacturer shall set the limit/travel stops at the required minimum or maximum valve opening. 9.5 LOCK-UP VALVES Air lock-up valves shall be specified for all services requiring the control valve to remain in position in case of instrument air supply failure. To prevent unintentional adjustments, the lock-up valves shall have a bolt adjustment provided with a locking facility, e.g. a locking nut. The lock-up valves shall be set 0.5 bar above the minimum instrument air supply pressure required by the actuator. For control valves with a valve positioner, the lock-up valve shall be installed between the positioner output and the actuator. If lock-up valves are fitted on valves operated by a solenoid valve, the solenoid valve shall be installed between the lock-up valve and the actuator. 9.6 LIMIT SWITCHES If limit switches are required, they shall be of the proximity type. The proximitor(s) and initiator should be mounted inside a box for mechanical protection. The flying leads of the proximitor(s) shall terminate in an attached terminal box; alternatively, the protection box and the terminal box may be combined into one box. These boxes shall be suitable for the electrical hazardous area classification in which they are located. If not armoured, the flying leads shall be protected against mechanical damage. If fitted, the external linkage between the actuator stem or rotary spindle and the initiator shall be protected against unintentional damage. Proximity switches shall be in accordance with DIN 19234. The valve Manufacturer shall follow the mounting instructions supplied by the limit switch Manufacturer. The valve Manufacturer shall properly adjust the limit switches. The vanes should approach the proximity switch perpendicular on its axis. Due consideration shall be given to the discrimination between the “closed” and “not closed” status of valves, especially for rotary valves without a dead angle, linear motion valves and valves with quick opening characteristics, with respect to the process requirements of the flow to be detected. Proximity switches shall be adjustable and shall function autonomously, e.g., one switch for the "fully open" position and a separate switch for the "fully closed" position. DEP 32.36.01.17-Gen. April 2003 Page 28 NOTE: If proximity switches are installed to detect a partially-open valve position, the vane shall be shaped so that a distinction can be made whether or not the partial open position has been reached/passed. Example: If an 80 % open position is to be detected, a logic ‘0’ might represent a valve opening between 0 % and 80 % and a logic ‘1’ not just a valve opening at 80 %, but any valve position of 80 % and above. The combination of proximitor and proximitor circuit shall be of fail-safe design for applications with a Safety Integrity Level 1 and above (see DEP 32.80.10.10-Gen.). For all other applications, fail-safe design is preferred, but cost aspects may justify the use of non-fail-safe limit switches. NOTE: If fail safe and non-fail safe limit switches are applied in a project, the fail-safe design should be used for all switches connected to the IPS and the non-fail-safe design for all other switches. This practical approach will provide flexibility during the engineering phase and limits the variety of input cards for IPS and DCS. 9.7 INSTRUMENT AIR BUFFER VESSELS 9.7.1 General Dedicated local instrument air buffer vessels are required for springless actuators of control valves, variable-pitch fans and dampers, if they must be driven to or held in a predefined position in the event of instrument air failure. Such air buffer vessels may also be required for actuators with springs to make them instrument air failure robust. Two types of design can be distinguished: Secured Instrument Air (SIA) design and the Manufacturer’s standard air buffer design. Plant safety reviews (e.g. a HAZOP or HSE desk review) should identify the applications for which a secured air supply is needed. NOTE: An air buffer vessel may require a safety relief device. 9.7.2 Secured Instrument Air design The secured instrument air supply shall maintain sufficient instrument air pressure in the buffer vessel to allow for at least three valve strokes within 30 min. Unless otherwise specified, the capacity of the secured instrument air buffer vessel shall be sized for a minimum pressure of 4.2 bar (ga) in the instrument air header. NOTE: One valve stroke is a movement from the fully open position to the fully closed position or vice versa. The specific design requirements for secured instrument air buffer vessels and associated instruments for depressuring systems, as discussed in DEP 32.45.10.10-Gen, apply to all applications requiring secured instrument air. The Principal shall approve air buffer vessel capacity calculations. 9.7.2 Manufacturer’s standard air buffer design For applications where the Manufacturer’s standard air buffer vessel designs are acceptable, the air buffer vessel capacity shall be sized for a minimum pressure of 4.2 bar (ga) in the instrument air header. The Principal shall approve air buffer vessel capacity calculations. 9.8 AIR LUBRICATORS Air lubricators shall be considered for pneumatic long-stroke cylinder actuators. Air lubricators shall be of the oil-mist type and the oil flow shall be externally adjustable. The oil buffer capacity shall be sufficient for continuous operation for one month. In addition, the lubricator shall have facilities for oil refilling under pressure, shall have oil level indication and shall be suitable for installing on a mounting plate. If air lubricators are used for valves operated by a solenoid valve, the lubricator shall be installed upstream of the solenoid valve. DEP 32.36.01.17-Gen. April 2003 Page 29 Spherical glass (bowl type) air lubricators shall not be used. 9.9 SOLENOID VALVES If solenoid valves are required, they shall be provided with a disc and/or seat of resilient material to achieve TSO. The air passages in the solenoid valves and the air tubing shall be large enough to achieve the opening or closing time of the valve as specified. If this would lead to unrealistically large passages and consequently high power consumption of the solenoid valve, consideration should be given to the use of quick-exhaust valves. To prevent plugging (e.g. during freezing periods), solenoid valves shall not be supplied with exhaust port protectors. Instead, they shall be provided with a piece of tubing bent downwards with the end cut off at an angle of 45°. Solenoid valves with flying leads shall be provided with a terminal box. If not armoured, the flying leads shall be protected against mechanical damage. To limit induction, DC solenoids shall be de-coupled with shunt diodes, connected directly across the solenoid terminals. For control valves with a valve positioner, the solenoid valve shall be installed between the positioner output and the actuator. Solenoid valves should be direct-operated. For large-volume actuators, a combination of a standard solenoid valve and separately mounted, pneumatically operated switching valve is preferred for its robustness to the use of a pilot-operated solenoid valve. If a pilot-operated valve is used, the air supply to operate the pneumatic valve should not be derived internally from the solenoid operated pilot valve, but from an external air supply connection. The use of pilot-operated solenoid valves requires the approval of the Principal. 9.10 FILTER REGULATORS An air filter regulator shall be installed in the instrument air supply line to the valve if the valve, actuator and/or accessories cannot operate safely at the upper design pressure of the instrument air header, see (8.1). NOTE: If the instrument air system is provided with relief valve(s), the upper design pressure of the instrument air header is the set pressure of such relief valve(s). The air filter regulators shall be of the reducing-relief valve type, with drainage facility and bolt adjustment provided with a locking facility, e.g. a locking nut, to prevent tampering. The air filter cartridges shall be of the rigid structure type to resist channelling, rupturing, shrinkage or distortion and shall have a maximum mesh size of 40 The capability, e.g. output capacity and required spring range, of the filter-regulator shall be checked against the instrument air requirement of the particular positioner and/or actuator or pneumatic instrument. Glass (bowl-type) filter regulators shall not be used. Filter regulators shall be mounted in the vertical position so that they are self-draining. Air filter regulators shall be fitted with small pressure gauges indicating the incoming instrument air supply pressure and delivery pressure to the actuator and/or its components. 9.11 FILTERS An air filter (i.e. without regulator) should be installed in the instrument air supply line to the valve if the valve, actuator and accessories can operate safely at the upper design pressure of the instrument air header. The air filter shall be provided with a manual drainage facility and a filter cartridge of the rigid structure type, to resist channelling, rupturing, shrinkage or distortion, and having a maximum mesh size of 40 DEP 32.36.01.17-Gen. April 2003 Page 30 Glass (bowl type) filters shall not be used. Filters shall be mounted in the vertical position so that they are self-draining. Air filters shall be fitted with small pressure gauges indicating the incoming instrument air supply pressure and delivery pressure to the actuator and/or its components. 9.12 QUICK-EXHAUST VALVES Quick-exhaust valves may be provided for on-off services that require the control valve to open or close faster than is possible with a standard actuator configuration. Fitting quick exhaust valves to throttling services may result in unstable operation and is therefore not recommended. Pilot-operated quick-exhaust valves shall not be used. To prevent plugging (e.g. during freezing periods), quick-exhaust valves shall not be supplied with exhaust port protectors. Instead, they shall be provided with a piece of tubing bent downwards with the end cut off at an angle of 45°. Quick-exhaust valves shall be fitted directly to the port of the actuator. 9.13 VOLUME BOOSTERS High capacity volume boosters shall only be provided if needed to achieve the specified stroking times. 9.14 RESTRICTORS If a throttling valve is required to be opened or closed slowly, this functionality should be implemented in the DCS or other remote electronic system. Mechanical instrument air restrictors should not be used for throttling valves. If used, a mechanical flow restrictor shall be provided with a lockable, variable restriction. For uni-directional restrictors, the direction(s) of restricted flow shall be indicated by a permanent mark on the body. If an air flow restrictor is fitted on a control valve equipped with a solenoid valve, care shall be taken in locating the restrictor relative to the solenoid valve. The restrictor shall only affect the required slow-opening or slow-closing of the control valve and shall not influence the other (unrestricted) valve movement. DEP 32.36.01.17-Gen. April 2003 Page 31 10. VALVE MARKING The control valve shall be provided with a standard stainless steel identification plate, showing the mandatory and supplementary marks as defined in IEC 60534-5. In addition, the TSO direction(s) shall be clearly marked where applicable by a permanent mark cast in or stamped on the valve body. Painted marks are not acceptable. Three-way valves shall clearly indicate the common inlet or common outlet port by a permanent mark "COMMON" stamped on the flange. Control valves affecting operational safety shall have warning plates, with text in white letters on a red background and stating, as appropriate, either: WARNING TRIM SIZE AFFECTS RELIEF VALVE CAPACITY or WARNING TRIM SIZE AFFECTS FIRING OF FURNACE Warning plates shall be attached by screws or rivets. DEP 32.36.01.17-Gen. April 2003 Page 32 11. INSPECTION AND TESTING 11.1 EXTENT The Manufacturer shall perform the following inspections and production tests (see Notes 1 through 4): Inspection/test Extent Method and acceptance criteria Examination and certification Valves in general service (as defined in MESC SPE 77/302) MESC SPE 77/302 Valves in special services (as defined in MESC SPE 77/303) MESC SPE 77/303 Dimensional inspection All valves (11.2) Hydrostatic test All valves (11.3) Functional test All valves (11.4) Hysteresis and dead band test for throttling valves Random sample (Note 4) (11.5) Seat leakage test Valves with Class V or Class VI tight shut-off requirement All valves (11.6) Other valves Random sample (Note 4) Capacity test Random sample (Note 4) (11.7) Low temperature test Valves with a lower design temperature ranging from minus 30 °C to minus 196 °C Type approval testing in accordance with specification T-2.253.730 Production testing: Sample in accordance with MESC SPE 77/306 (11.8) Vacuum test Valves in vacuum service Sample in accordance with MESC SPE 77/307 MESC SPE 77/307 Fugitive emission test Valves used in services requiring a fugitive emission limitation Sample in accordance with MESC SPE 77/312 MESC SPE 77/312 NOTES: 1. The selected valves for each test shall be listed by the Contractor and approved by the Principal. 2. Inspection and testing shall include accessories if part of the supply. 3. The test results shall be made available as part of the package of final certified documents. 4. The Principal shall approve the number of valves sampled. 11.2 DIMENSIONAL AND FLANGE FACE FINISH CHECK The face-to-face dimensions shall be as given in the relevant standard (4.4). All dimensions (including overall height) shall be as shown on the Manufacturer's drawings. The flange face finish shall be checked (4.3). 11.3 HYDROSTATIC TEST Hydrostatic testing shall be in accordance with IEC 60534-4, with the test duration as follows: Valve size Test duration ≤ DN 80 to DN 200 2 min ≥ DEP 32.36.01.17-Gen. April 2003 Page 33 For carbon steel valves and low alloy steel valves, the hydrostatic test fluid shall be potable water with a chloride content of maximum 200 mg/kg. Austenitic and duplex stainless steel valves and valves made of 9 % nickel alloy shall be hydrostatically tested with potable water with a chloride content of 50 mg/kg or less. These valves shall be flushed with condensate or demineralised water (chloride content of 2 mg/kg maximum) immediately after the hydro test. All valves shall be drained immediately after the test and shall be thoroughly dried immediately after draining. 11.4 FUNCTIONAL TEST The control valve shall be completely assembled and fitted with all accessories such as positioner, solenoid valve(s), etc. The valve positioner shall be checked for correct calibration. The stroking time at the specified air pressures shall comply with the requirements given in this document (see 8.3). All required stroking times shall be checked during the fuctional testing. If the control valve is equipped with a hand wheel, it must be possible to fully open and close the valve using the hand wheel; see (9.3). If the control valve is equipped with limit switches, they shall be checked for functional operation with a proximity tester. 11.5 HYSTERESIS AND DEAD BAND TEST For definitions and test procedures, refer to IEC 60534-1 and IEC 60534-4. The actuating medium for the tests shall be clean, dry air or nitrogen. Testing shall be performed under atmospheric conditions (at zero differential pressure and ambient temperature) and with the minimum specified air supply pressure. The following sequence of input signals: 50 %, 75 %, 100 %, 75 %, 50 %, 25 %, 0 %, 25 % and 50 %. For PTFE-based packing, the hysteresis shall not exceed 1.0 % of maximum valve stroke. The 5 %, 50 % and 95 % of the input span. For PTFE-based packing, the maximum dead band found shall not exceed 2 % of rated input signal. For packing other than PTFE, the maximum hysteresis and dead band shall be quoted by the Manufacturer for approval by the Principal. All test results shall be documented. 11.6 SEAT LEAKAGE TEST The seat leakage test shall be in accordance with IEC 60534-4, with the acceptance criteria for the specified shut-off class; see (3.1) for TSO class V or VI. If the shut-off class is not specified, the following acceptance criteria shall apply: Acceptance criteria Single-seated valves Class III Double-seated valves Class II For each valve tested, the Manufacturer shall state the following data: - flow direction; - test medium; - test differential pressure; DEP 32.36.01.17-Gen. April 2003 Page 34 - seat leakage flow rate measured; - allowable seat leakage flow rate; - seat leakage class (if applicable). 11.7 CAPACITY TEST The actual C 11.8 LOW TEMPERATURE PRODUCTION TEST Low temperature production testing shall be in accordance with MESC SPE 77/306. In addition, a hysteresis and dead band test (11.5) shall be performed at the temperature of the low temperature test. 11.9 WITNESSING BY PRINCIPAL The extent of the Principal's involvement in witnessing inspections and tests at the Manufacturer's works shall be stated in the requisition. DEP 32.36.01.17-Gen. April 2003 Page 35 12. DOCUMENTATION The document requirements to record the valve selection process (2.2) shall be as specified in the requisition. It should include at least: - calculations of control valve capacity (C where applicable, details of the secured instrument air vessel; - details of the selected actuator and torque or thrust figures; For spare part requirements, see DEP 70.10.90.11-Gen
|
|
|
|
|
|
|
|
The difference between whole current meter and CT meter is whole current meter is without current transformer and the CT meter is with current transformer (CT). |
Whole current meter will measure the actual current directly without using the transformer. CT meter will have current transformer to reduce the high current to low current and the meter connected to CT will give the reduce current reading equivalent... |
A poor man had no land and prayed to God for some land. God appeared to him and told him that all that he could cover from dawn to dusk would be his land. The man set off the next morning without sleeping a wink. Though he had covered enough land... |